DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 100
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
RF Receiver Supervision Interval
• Address: 1250
• Default: 5 (24 h)
• Selections:
- 0 = No Supervision
- 1 = 1 h
- 2 = 2 h
- 3 = 4 h
- 4 = 12 h
- 5 = 24 h
RF transmitters (sensors) send a supervisory signal approximately once every 13 min. The RF receiver
expects to hear this signal from every transmitter in the interval determined in this parameter. A
“Missing” report is sent for each device that the RF Receiver does not hear.
Fire transmitters have a fixed supervision interval of 4 h.