DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 68
3.4 User Interface
3.4.1 PIN Configuration/Installer PIN
A Personal Identification Number (PIN) is a unique number issued at the time of installation of each
system. This PIN is required to operate the system (arm/disarm, test system, initiate functions, etc.).
The PIN is not the same as the account number.
PIN Length
Address: 0379
Default: 4 (4 digits long)
Selections: 3 to 7 (3 digits min; 7 digits max)
This parameter determines the number of digits in a PIN. All user PINs and the Installer PIN follow this
length.
If the PIN length is shortened after PINs are entered, duplicate PINs could be created (for
example, PINs 1235 and 1238 would both become 123).
User Tamper Options
Address: 0380
Default: 0
Selections: 0 to 3
Enter This Data Digit to Select Options
User Tamper Options
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
No User Tamper Options
User Tamper {156} Reports Enabled
User Tamper Activates Burg Alarm Output
Reserved
Reserved
A user tamper event is:
- A user entering a PIN that is not in the system (the user must enter the invalid PIN the number
of times shown in User Tamper Retry Count on page 69).
- A user entering a PIN that is in the system but does not have the authority for the desired
function.
User Tamper Reports Enabled: If enabled, this option ties User Tamper {156} reports and user
tamper activated alarm outputs to the keypad’s area. If only the “User Tamper Reports Enabled”
option is selected and there is a user tamper event, the text keypad where the event occurs shows
“Keypad locked!”
User Tamper Activates Burg Alarm Output: If the burglary alarm output (steady alarm output) is
selected and there is a user tamper event, the text keypad where the user tamper occurred shows
“Keypad locked!” Other text keypads in the area show “Usr Tamper Alarm, Enter PIN to silence.”
During the time the keypad is locked out, any key pressed produces an error tone (for text and
LED keypads). Selecting the “User Tamper Activates Burg Alarm Output” option specifically
activates output functions 1|8, 1|9, 1|10, and 8|8. See Table 34 on page 88 for descriptions of
these output functions.