DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 83
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
Location ##, Zone Function
• Address: See Table 30 on page 80
• Default: See Table 30 on page 80
• Selections: 0 to 15 (see Table 31 for Default Zone Function Types)
The zone function determines how the system responds to changes on the sensor loop assigned to
the location. There are two general categories of zones:
24-hour and Controlled.
• 24-hour Zone: 24-hour zones are always on and cannot be turned off by the user. Faults on 24-
hour zones prevent turning the system on.
• Controlled Zone: Controlled zones are turned on and off when the user turns the system on
(armed) and off (disarmed).
See Table 31 for default zone function selections.
Table 31: Default Zone Function Type Selections
Default Zone Function Type
0 Disabled
1 24-hour Fire, Normally-Open Contact
2 24-hour Fire with Alarm Verification, Normally-Open Contact
3 24-hour Voice Active Control Input, Normally-Open Contact with EOL
4 24-hour Tamper (no EOL resistor)
5 24-hour Emergency (no alarm output)
6 24-hour Visible Panic (no alarm output)
7 24-hour Invisible Panic (no alarm output)
8 24-hour Burglary
9 Chime Mode only
10 Controlled Keyswitch, Momentary, All On, Off from Any Armed State
11 Controlled Entry/Exit Delay 1
12 Controlled Entry/Exit Delay 2
13 Controlled Follower
14 Controlled Instant
15 Controlled Instant (Perimeter)
Location ##, Area
• Address: See Table 30 on page 80
• Default: Area 1
• Selections:
- 0 = No Area Assigned (Disabled)
- 1 = Assign Location ## to Area 1
- 2 = Assign Location ## to Area 2
- 3 = Assign Location ## to Area 3 (DS7240V2 only)
- 4 = Assign Location ## to Area 4 (DS7240V2 only)
This parameter assigns an area to a location. Each location can only be assigned to one area.