Steady, Pulse, and One-Shot Mode Configuration
• Steady and Toggle Modes: These modes are not affected by the Time Base and Time Multiplier
parameters (see Table 36 and Table 37).
• Pulse Modes: The system calculates the On Time (activation) and the Off Time for outputs based
on the values in the Base and Multiplier columns (see Table 36). The duration, or On Time, of an
output is determined by selecting one of the four Base options from Table 36. Calculate the Off
Time by multiplying the Base by the Multiplier.
The Time Base of 200 ms in Table 36 and Table 37 is only available for on-board outputs.
Table 36: Pulse Mode Configuration
On Time
(On Time = Time of
Base)
Off Time
(Off Time = Base x
Multiplier)
0 0 N/A Always Off N/A
1 (200
ms)
200 ms 01 to 99 200 ms to 19.8 sec ±200 ms
2 (1 sec) 1 sec 01 to 99 1 to 99 sec ±1 sec
3 (1 min) 1 min. 01 to 99 1 to 99 min. ±1 min.
4 (1 h) 1 h 01 to 99 1 to 99 h ±1 h
• One Shot Modes: The duration of the On Time of a One Shot output is determined by multiplying
the Base by the Multiplier.
Table 37: One Shot Mode Configuration
On Time
(On Time = Base x
Multiplier)
0 N/A 0 N/A
1 (200
ms)
01 to 99 200 ms to 19.8 sec ±200 ms
2 (1 sec) 01 to 99 1 to 99 sec ±1 sec
3 (1 min) 01 to 99 1 to 99 min. ±1 min.
4 (1 h) 01 to 99 1 to 99 h ±1 h