DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 94
Table 35: Output Mode Options (continued)
Mode
Mode Type
Output
Type
Description
9 Latch,
Reversed
Logic Normal
State Output turns off when the condition is active and remains off until [System Reset] is
pressed.
Event Output turns off when the event occurs and remains off until [System Reset] is
pressed.
10 Pulse,
Reversed
Logic Normal
State When the condition is active, the output pulses. When the condition is inactive, the
output is on.
Event When the event occurs, the output pulses. The output continues pulsing until [System
Reset] is pressed, then turns on.
11 One-Shot,
Reversed
Logic Normal
State When the condition changes from inactive to active, the output turns off. The output
turns on at the end of the One-Shot time. While the output is off, any changes in the
condition are ignored.
Event When the event occurs, the output turns off and remains off for the One-Shot time.
While the output is off, a second event does not affect the output.
12 One-Shot
with Re-
Trigger,
Reversed
Logic Normal
State When the condition changes from inactive to active, the output turns off and remains
off for the One-Shot time. If the condition goes inactive and active again, the One-
Shot time is restarted and the output remains off.
Event When the event occurs, the output turns off and remains off for the One-Shot time. If
a new event occurs, the One-Shot time is restarted and the output remains off.
13 One-Shot
with Reset,
Reversed
Logic Normal
State When the condition changes from inactive to active, the output turns off and remains
off for the One-Shot time. If the condition goes inactive, the output is turned on early.
Event When the event occurs, the output turns off and remains off for the One-Shot time.
[System Reset] turns the output on early.
Base, Output ##
Address: See Table 33 on page 86
Default: See Table 33 on page 86
Selections:
- 0 = Disabled
- 1 = 200 ms (on-board outputs only)
- 2 = 1 second
- 3 = 1 minute
- 4 = 1 hour
Multiply the Base with the Multiplier to determine the output’s timing. See Table 36, on page 93, and
Table 37, on page 95.
Multiplier, Output ##
Address: See Table 33
Default: See Table 33
Selections: 0,0 to 9,9
Multiply the Base with the Multiplier to determine the output’s timing. See Table 36 and Table 37.