2.6.11 DX2010 Supervision
The control panel supervises communication to
the DX2010. If it fails to communicate with the
DX2010, it sends a “DBus Missing” {125} report.
2.7 Off-board Output Setup
(DX3010)
2.7.1 Overview
The DX3010 Octo-Output Expander allows you to
add outputs to your system in groups of eight.
The DS7240V2 supports up to 20 programmable
outputs (4 on-board, 16 off-board using two
DX3010 Output Expanders).
The DS7220V2 supports up to 12 programmable
outputs (4 on-board, 8 off-board using one
DX3010 Output Expander).
The DX3020 X-10 Interface Module allows the
control panel to control up to 16 X-10 modules.
The DX3020 emulates up to 2 DX3010 modules.
You can assign any of the programmable output
functions to the DX3010’s individual outputs
separately. See Output Parameters on page 86 for
programming details.
Current Draw: 10 mA Standby plus 40 mA for
each energized output (relay) for a total of 330
mA maximum with all eight outputs energized.
See the DX3010 Installation Guide (P/N: 49529)
for complete installation, addressing and
operating instructions.
2.7.2 DX3010 Relay Outputs
Outputs can activate when setting the
DX3010’s address DIP switches,
programming the control panel,
resetting the control panel or applying
power to the control panel.
Disconnect equipment connected to
outputs when performing these
functions.
The DX3010 relay outputs are not
supervised and cannot be used in fire
or combined fire/burglary installations
for primary indicating devices.
Each DX3010 output provides a Form “C” dry
contact rated for 5.0 A at 28 VDC. Normally-
Open, Common, and Normally-Closed terminals
are available for each relay output. When an
individual output is activated, there is continuity
between the Normally-Open and Common
terminals. When the output is not activated, there
is continuity between the Normally-Closed and
Common terminals.
2.7.3 DX3010 Installation
The DX3010 contains static-sensitive
components. Follow anti-static
procedures when handling this
module.
You can install the DX3010 in the control panel’s
enclosure with the hardware supplied with the
DX3010. See Figure 39.
Figure 39: DX3010 to Control Panel
Enclosure Installation
1- Control panel board location
2- DX3010 installation locations
3- DX3010 terminal block
4- Enclosure wall
5- Screws (supplied with DX3010)