DS7200V2-EXP | Installation Guide | 2. System Installation
and Setup
EN | 20
2.3.5 No EOL Zone Configuration
See Figure 18 when wiring a zone with no EOL
resistors.
Figure 18: Single Zone Sensor Loop
Wiring
(No EOL)
1- Sensor loop terminal
2- Common
3- Sensor loop terminal
4- Common
5- 100 Ω maximum
6- Normally-Open contacts
7-
Normally-Closed contacts
2.3.6 Four-Wire Smoke Detector
Configuration
A four-wire smoke detector can be connected to
any of the control panel’s on-board sensor loops
(L-1 to L-8). A four-wire smoke detector must use
a relay module to interrupt power to the detector
in order for the detector to reset.
Configure the output controlling the relay as
Output Function 1|13 “Fire Verification” (see
Output Parameters on page 86 for more
information).
Make loop connections to L-X (where X = Loop #)
and COM terminals. See Figure 19, and Figure 20
on page 21.
Figure 19: 4-wire Smoke Detector
(Tamper-wired)
1- Remove jumper plug from PO 1 SELECT
jumper
2- 2.2 kΩ alarm resistor
3- 2.2 kΩ EOL resistor
4- Smoke detector
5- AUX (+)
6- AUX (-)
5
4
2
3
1
6
7
BATT+
BATT-
ALRM
+
PO1
SMK
+
PO1 SELECT
4
1
2
3
5
6
A
B COM
L-1