DS7200V2-EXP | Installation Guide | 2. System Installation
and Setup
EN | 17
Keyswitch Wiring Single EOL Configuration
For maintained switches, connect the EOL
resistor for the zone at the keyswitch so that the
switch opens the circuit when it operates. A
short on the circuit produces an alarm if the area
is armed and a trouble if it is disarmed. See
Figure 11.
Figure 11: Maintained Keyswitch:
Single EOL Resistor
Configuration
1- Zone input
2- Common
3- 2.2 kΩ resistor
4-
Keyswitch (Open on circuit arms area)
For momentary switches, connect the EOL
resistor for the zone at the keyswitch so that the
switch shorts the resistor when it operates. An
open on the circuit produces an alarm if the area
is armed and a trouble if it is disarmed. See
Figure 12.
Figure 12: Momentary Keyswitch:
Single EOL Resistor
Configuration
1-
Zone input
2- Common
3- 2.2 kΩ resistor
4- Keyswitch (Short on circuit toggles arming
state)
Keyswitch Wiring Zone Doubled
Configuration
For maintained or momentary operation, wire the
keyswitch as shown in Figure 13.
Figure 13: Keyswitch: Zone Doubled
Configuration
1- Zone input
2- Common
3- Second zone wiring
4- 2.2 kΩ or 3.65 kΩ resistor
5-
Keyswitch
Keyswitch Wiring No EOL Resistor
Configuration
For maintained or momentary operation, wire the
keyswitch as shown in Figure 14.
Figure 14: Keyswitch: No EOL Resistor
Configuration
1- Zone input
2- Common
3-
Keyswitch
3
1
2
4
3
4
1
2
4
3
5
1
2
1
2
3