Miscellaneous Issues
Problem
Cause
Solution
There are numbers in
braces {###} throughout
this manual.
These numbers {###} refer to the
event numbers described Control
Panel Events and Reporting Formats
on page 108.
N/A
My printer is printing
strange characters and I
cannot read it.
The settings for the DX4010 RS-
232 Serial Interface Module can
cause unexpected printer output.
Verify the settings for the following parameters
(see the DS7200V2 Expert Programming Guide
P/N:4998153891):
“DX4010 Output Configuration” (Address
1253)
“Baud Rate Configuration” (Address 1254)
“Parity/Flow Control/Stop Bit
Configuration” (Address 1255).
Network communication is
not working as expected.
The DX4020 Network Interface
Module is not properly wired
and/or configured.
The control panel is not
properly programmed for
network communication.
Make sure the DX4020 is properly
connected to the control panel. See
DX4020 Wiring on page 37.
Make sure the DX4020’s DIP switches are
set to Address 134 (see DX4020
Addressing on page 36).
Make sure your selection for Address 3541
includes the “Alternate Communication
Interface at Address 134” option. See
Network Interface Module Options on page
105.
See the DX4020 Installation Guide
(P/N: 49522) for additional configuration
requirements.
Make sure you are using a valid IP address
and that you entered it correctly. See IP
Address 1 (2) for Destination 1 (2) on page
101.
Make sure selection for Alternate
Communication Options (see page 102)
includes the “Enable Alternate
Communication” option.
4.3 Data Bus Address Quick Reference
Table 41: Data Bus Address Quick Reference
Data Bus Address
Device Description
0 Installer Keypad or local connection to RPS
1 to 8 Keypads 1 to 8
40, 41
DX8010 Telephone Control Module
50 Premises RF Receiver 1
51 Premises RF Receiver 2
52 to 55 Premises RF Keypads Receiver 1
60 to 63 Premises RF Keypads Receiver 2
101 to 107 DX2010 Wired Input Expanders
134 DX4020 Network Interface Module (NIM)
150, 151 DX3010 Output Expanders and/or DX3020 X-10 Interface Module
250 DX4010i/DX4010 Serial RS-232 Interface Module