DS7200V2-EXP | Installation Guide | 4. Reference Materials
EN | 120
4.2 Troubleshooting
Use this section to troubleshoot problems with the control panel.
Below are various problems that may occur, followed by explanations of the problems (cause) and
solutions.
Arming Issues
Problem
Cause
Solution
I enter a valid PIN to arm an
Area, but the Area does not
arm.
No zones are programmed for that
Area.
User does not have the
appropriate Authority Level to arm
system.
Must press On or Perimeter Only
keys.
Add a minimum of one zone to each
Area.
Make sure users who should be
able to arm/disarm the system have
the appropriate Authority Level.
I cannot tell if my system is
armed for Perimeter Only or
Partial On from a
DS7445i/DS7445V2 LED
Keypad.
The keypad turns the Perimeter Only
LED on for both of these arming
options, but cannot distinguish
between the two.
There is no solution. The user who arms
the system must know which keys were
pressed ([Perimeter Only] or [#][2] for
Perimeter Only; [#][3] for Partial On).
I armed my system All On, but
it keeps changing to Perimeter
Only.
The “All On-No Exit” arming option is
enabled. When the panel was armed,
nobody faulted an Entry/Exit Delay
zone, therefore the panel did not arm
those internal zones.
See Arming Options 1on page 62
(Address 0258) to disable this option.
I am using an exit terminator
switch. When I try to arm, the
keypad does not show any
delay.
Exit delay set to zero. Do not use exit delay set to zero with
exit terminator. Set for at least ten sec.
Zone Issues
Problem
Cause
Solution
I have a trouble on a
keyswitch zone and it does
not clear. The zone is restored
to its normal condition.
Swinger Shunt on a keyswitch might
be enabled on this Zone Function. The
zone does not restore until the
Swinger Shunt condition restores.
Arm and disarm the system to clear the
current trouble. To prevent this in the
future, check the Keyswitch Zone
Function programming and make sure
Swinger Shunt is disabled. See the
DS7200V2 Expert Programming Guide
(P/N: 4998153891) for complete zone
function programming instructions.
There is no output after
alarming a zone.
Incorrect programming. Review the following sections to see if
the output is correctly programmed:
See “Options 2, Zone Function ##
in the DS7200V2 Expert
Programming Guide (P/N:
49981
53891).
See Output Parameters on page 86.