DS7200V2-EXP | Installation Guide | 2. System Installation
and Setup
EN | 40
2.11 System Power Up
The system shows a trouble upon any power-up
because the date and time settings are missing.
This trouble remains until these settings are
made.
To reduce the occurrence of false
alarms upon panel power-up (or
restoration of power after a complete
loss of primary and secondary power),
the control panel ignores all zone
faults for approximately 60 sec while
the devices stabilize.
2.12 System Status LED
Figure 61 shows the location of the control
panel’s system status LED. Table 19 shows the
LED’s response to system conditions.
Figure 61: System Status LED
1- Control panel system status LED
Table 19: System Status LED Operation
Condition
LED Response
System Normal On for 50 ms, off for 1 sec.
Battery Missing Off for 200 ms, on for 1 sec.
AC Missing Off for 200 ms, on for 200
ms, off for 200 ms, on for 1
sec.
Phone Ringing Flickers for 1 sec. As each
ring is detected.
Phone Line Seized
(control panel using
phone line)
On solid.
Shut Down (system
voltage below 10.2
VDC)
Off for 200 ms, on for 200
ms, off 200 ms, on 200 ms,
off 200 ms, on for 1 sec.
2.13 Installer Keypad
A text keypad can be configured as an Installer
Keypad.
This keypad is not intended for permanent
installation and must remain with the
installer/service technician.
Use the color-coded keypad wire assembly
supplied with the control panel (P/N: 15-04298-
0000) to connect the Installer Keypad to the
control panel’s Aux/Data pins. See Figure 62.
Figure 62: Installer Keypad to Control
Panel Wiring
1- DS7447E/DS7447V2 Text Keypad terminal
block
2- Red (+) wire
3- Black (-) wire
4- Green (G) data wire
5- Yellow (Y) data wire
6-
Control panel board
The Installer Keypad must be set to
Address 0 (set MODE to OFF) and the
Installer Switch must be closed to use
the Installer Keypad.
BATT+
BATT-
ALRM
+
PO1
L-1
SMK
+
L-2COM
L-4COML-3 L-6COML-5
L-8COML-7
T
T1
R1
AUXILIARY
PO1 SELECT
A B
R
STATUS
1
1
2
3
4 5
6
Bat+
Bat-