EN | 39
You can use either one of the Aux Power (-)
terminals and either one of the 12 VDC (+)
terminals when connecting devices to the control
panel.
Figure 59: DACM to Control Panel Wiring
1- DACM
2- Control Panel
3- Wire Harness (supplied with DACM)
4- Green (G) wire
5- Yellow (Y) wire
6- Black (-) wire
7- Red (+) wire
You can use either one of the Aux Power (-)
terminals when connecting to the control panel.
Do not tie the black (-) output to
earth ground when using any external
power supply. A ground fault
condition is reported if black (-) is
grounded.
Figure 60: DACM to Control Panel Wiring
(External Power Supply)
1- DACM
2- Control Panel
3- Wire Harness (supplied with DACM)
4- Green (G) wire
5- Yellow (Y) wire
6- Black (-) wire
7- Red (+) wire
8-
External 12 VDC power supply
2.10.3 DACM Supervision
The control panel supervises communication to
the DACM. If it fails to communicate with the
DACM, it sends a “DBus Missing” {125} report.