EasyManua.ls Logo

Bosch DS7200V2-EXP - Figure 59: DACM to Control Panel Wiring; Figure 60: DACM to Control Panel Wiring (External Power Supply)

Bosch DS7200V2-EXP
138 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DS7200V2-EXP | Installation Guide | 2. System Installation
and Setup
EN | 39
You can use either one of the Aux Power (-)
terminals and either one of the 12 VDC (+)
terminals when connecting devices to the control
panel.
Figure 59: DACM to Control Panel Wiring
1- DACM
2- Control Panel
3- Wire Harness (supplied with DACM)
4- Green (G) wire
5- Yellow (Y) wire
6- Black (-) wire
7- Red (+) wire
You can use either one of the Aux Power (-)
terminals when connecting to the control panel.
Do not tie the black (-) output to
earth ground when using any external
power supply. A ground fault
condition is reported if black (-) is
grounded.
Figure 60: DACM to Control Panel Wiring
(External Power Supply)
1- DACM
2- Control Panel
3- Wire Harness (supplied with DACM)
4- Green (G) wire
5- Yellow (Y) wire
6- Black (-) wire
7- Red (+) wire
8-
External 12 VDC power supply
2.10.3 DACM Supervision
The control panel supervises communication to
the DACM. If it fails to communicate with the
DACM, it sends a “DBus Missing” {125} report.
2
BATT+
BATT-
1
6
7
5
4
3
(+) (-)
8
2
BATT+
BATT-
1
6
7
5
3
4

Table of Contents