Loading...
DS7200V2-EXP | Installation Guide | 2. System Installation
and Setup
EN | 32
See Figure 44 and Figure 45 for power wiring
connections.
Figure 44: DX4010i to Control Panel
Wiring
1-
DX4010i board
2- Control panel board
3- Black (-) wire
4- Green (G) data wire
5- Yellow (Y) data wire
6-
Red (+) wire
You can use either one of the Aux Power (-)
terminals and either one of the 12 VDC (+)
terminals when connecting devices to the control
panel.
If you need to power the module from an external
power supply, connect it to the power supply and
the control panel as shown in Figure 45.
Figure 45: DX4010i to Control Panel
Wiring (External Power Supply)
1- DX4010i board
2- Control panel board
3- Black (-) wire
4- Green (G) data wire
5- Yellow (Y) data wire
6- Red (+) wire
7-
External 12 VDC power supply
You can use either one of the Aux Power (-)
terminals when connecting to the control panel.
Do not tie the black (-) output to
earth ground when using any external
power supply. A ground fault
condition is reported if black (-) is
grounded.
BATT+
BATT-
1
4
6
3
5
2
BATT+
BATT-
1
4
3
5
2
6
(+) (-)
7

Table of Contents