DS7200 Installation Guide
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
Prioritization of signals & indicators
Incoming signals are prioritized in chronological order. All signals are processed within 10 s.
Indicators displayed individually with text.
The control panel can meet all the options in Table 13, regarding notification outputs in the European standard for Intrusion
Systems.
Zone expanders
The zone expenders should be mounted inside the control panels enclosure for EN-approved systems.
Classification
DS7200 meets the Security Grade 2, Environmental Class 2
Current and battery capacity
Max current draw
(Panel excluded)
400 ma 7,2 Ah 12 hours EN
800 mA 2 x 7,2 Ah 24 hours EN
1 A 18 Ah 48 hours EN
1,2 A 7-18 Ah - Non approved
Code combinations
The number of code combinations:
4-digit code allows for 10,000 combinations
5-digit code allows for 100,000 combinations
6-digit code allows for 1 million combinations
7-digit code allows 10 million combinations
The number of free combinations = code combinations – number of users
Weight and dimensions
Material: 1.0 mm thick cold-rolled steel
Dimensions (H x W x D): 36.8 x 31.8 x 7.6 cm
Weight 5.5 kg