EasyManua.ls Logo

Bosch DS7200V2-EXP - Table 23: Personal Dialing Format Configuration; Table 24: Report Tone Selections

Bosch DS7200V2-EXP
138 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 52
Address: See Table 23
Default: See Table 23
Selections: 0 to 15
Table 23: Personal Dialing Format Configuration
Event
Group
Address
Personal Dialing Format
Code
Data Digit
Default
1 3414 Duress 0
2 3415 Fire Alarm 1
3 3416 Non-fire Alarm 2
4 3417 Reserved 0
5 3418 Fire Trouble 5
6 3419 Non-fire Trouble 6
7 3420 Fire Restoral 0
8 3421 Non-fire Restoral 0
9 3422 RF Trouble 0
10 3423 Open/Close 0
11 3424 Installer Mode 0
12 3425 System Fault 8
13 3426 Test Report 0
14 3427 Reserved 0
15 3428 Bypass 0
16 3429 Output/User 0
Use this parameter to select the tone for the 16 different Personal Dialing Format event groups.
For each event group, the report is programmed as a value from 0 to 15. If 0 (zero) is programmed, no
report is sent and the event is a Local Only event.
See Table 24 for the two-digit report tone when the value entered is non-zero (1 to 15).
Table 24: Report Tone
Selections
Data Digit
Selection
Report Tone
0 None
1 1 0
2 1 1
3 2 0
4 1 2
5 2 1
6 3 0
7 1 3
8 2 2
9 3 1
10 4 0
11 1 4
12 2 3
13
3 2
14 4 1
15 5 0