DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 82
Zone Doubling Programming
Zone doubling requires 3.65 k and 2.2 k EOL resistors as shown in Table 30. If zone
doubling is not used, see “On-board Location EOL Resistor Value” and “DX2010
Configuration Options” in the DS7200V2 Expert Programming Guide (P/N: 4998153891) for
on- and off-board zone EOL resistor configuration.
To use both on-board and off-board zone doubling at the same time, use the following steps:
1. Double Locations 1 to 8 with Locations 9 to 16.
a. Set the Device Type for Locations 1 to 16 to 1 (on-board).
b. Set Address 1026 (On-board Location EOL Resistor Value) to 4 (Zone doubled, 2.2 k &
3.65 k EOL resistors).
c. Use 3.65 k EOL resistors on Locations 1 to 8, and 2.2 k EOL resistors on Locations 9 to
16.
2. Double Locations 25 to 32 with Locations 33 to 40.
a. Set the Device Type for Locations 25 to 40 to 3 (DX2010 zone doubled).
b. Set the DX2010’s DIP switches to Address 107 (Locations 25 to 40). See Table 10 on
page 28.
c. Use 3.65 k EOL resistors on Locations 25 to 32, and 2.2 k EOL resistors on Locations
33 to 40.
Locations 17 to 24 cannot be used for zone doubling when doubling on-board and off-
board zones at the same time. These locations can still be used as RF zones, or as non-
doubled zones.
Location ##, Device
Address: See Table 30 on page 80
Default: See Table 30 on page 80
Selections:
- 0 = No Device Assigned (Disabled)
- 1 = On-board Zone (L-1 to L-8)
- 2 = Wired Zone Expander (DX2010) (configured for 8 inputs)
- 3 = Wired Zone Expander (DX2010) (configured for 16 inputs [zone doubled])
- 4 = RF Receiver 1 (see Data Bus Device Parameters on page 99)
- 5 = RF Receiver 2 (see Data Bus Device Parameters on page 99)
- 6 = DACM Door Contact (see
DACM Configuration
on page 105)
Each location in the control panel can be assigned to one of four types for devices:
The control panel’s on-board sensor loops (L-1 to L-8)
A DX2010 Input Expander
A Data Bus RF Zone Expander (Receiver 1 or Receiver 2)
A DACM’s door contact
Use each location’s device parameter to assign the location to a device type.