DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 106
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
Keypad/Door Access Control Module (DACM) Area Options
• Address:
- Keypad/DACM 1: 0679
- Keypad/DACM 2: 0681
- Keypad/DACM 3: 0683
- Keypad/DACM 4: 0685
- Keypad/DACM 5: 0687
- Keypad/DACM 6: 0689
- Keypad/DACM 7: 0691
- Keypad/DACM 8: 0693
• Default:
- Keypad/DACM 1: 1 (Device is a keypad/DACM assigned to Area 1)
- Keypads/DACMs 2 to 8: 0 (No keypad/DACM assigned)
• Selections: 0 to 4, 9 to 12
Enter This Data Digit to Select Options
Keypad/DACM not assigned (disabled)
Assign Keypad/DACM to Area 1
Assign Keypad/DACM to Area 2
Assign Keypad/DACM to Area 3 (DS7240V2
only)
Assign Keypad/DACM to Area 4 (DS7240V2
only)
This parameter identifies the device connected to the control panel’s Data Bus (Addresses 1 to 8) as a
DACM, and assigns the DACM to an area.
The control panel supervises the connection to the DACM. If it fails to communicate with the control
panel, the control panel sends a “DBus Missing” {125} report.
DACM Location Assignment
• Address:
- DACM 1: 3546 to 3547
- DACM 2: 3548 to 3549
- DACM 3: 3550 to 3551
- DACM 4: 3552 to 3553
- DACM 5: 3554 to 3555
- DACM 6: 3556 to 3557
- DACM 7: 3558 to 3559
- DACM 8: 3560 to 3561
• Default: 0,0
• Selections:
- DS7240V2: 0,0 to 4,0
- DS7220V2: 0,0 to 2,4
A DACM door contact can occupy any location in the control panel. Use this parameter to assign a
control panel location to a DACM door contact.