DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 66
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
Area # Opening {89-96}/Closing {42-67} Reporting Options
• Address:
- Area 1: 0296
- Area 2: 0318
- Area 3 (DS7240V2 only): 0340
- Area 4 (DS7240V2 only): 0362
• Default: 1
• Selections: 0, 1, 3, 5, 7, 9, 11, 13, 15
Enter This Data Digit to Select Options
Area # Open/Close Reporting Options
No Open or Close Reports for Area #
Open/Close Reports (for All On) for Area #
Enabled
Restrict Open/Close Reports; Open after Alarm,
Close on Force Arm
Open/Close Reports for Perimeter Only (and
Partial On) Mode – Must also select Open/Close
Reports (for All On)
1 Second Bell Test on Closing Rpt
Acknowledgement
• Open/Close Reports for Area # Enabled: If enabled, this option configures Opening/Closing
reports for each area. This also includes the report for the Extend Auto Closing {21} event.
Opening {89 to 96} and Closing {42 to 67} reports must be enabled at the system level. Opening
and Closing reports are also enabled by authority level. Reporting must also be enabled at the
system level (see Global Reporting Options on page 58).
• Restrict Open/Close Reports; Open From Alarm, Close on Force Arm: If this option is enabled,
the control panel only sends opening reports when the user disarms the system after an alarm and
when Bell Time has expired. The control panel only sends closing reports when a zone is force-
armed. Force arming is set by authority level and by zone function configuration.
Enabling the “Restrict Open/Close Reports” option overrides the “First Area to Open/Last
Area to Close Reporting” option. See Arming Options 2 on page 63 for more information on
the “Restrict Open/Close Reports” option.
• Open/Close Reports for Perimeter Only Mode: If this option is enabled, the control panel sends
closing reports when users arm the system Perimeter Only. If any zones are bypassed, bypass
reports are also sent. The control panel sends opening reports when users disarm the system.
Perimeter Only arming is set by authority level and by Zone Function configuration.
• 1 Second Bell Test on Closing Ack: If this option is enabled, outputs assigned to Alarm Output
Functions 1|8, 1|9, 1|10, and 8|8 activate for one sec. See Function, Output ## on page 88 for
output function descriptions.