DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 89
Table 34: Output Function Types (continued)
Digit
1
Digit
2
Function Type
Description
0 11 Exit Delay, Entry Delay, Chime Output activates at the start of Exit Delay or Entry Delay. For Steady or
Pulse modes, the output remains activated until Entry or Exit Delay ends.
The output also activates whenever a Chime zone is faulted.
The output
does not activate on Chime if Chime Tone is turned off.
0 12 Phone Line Fail Output activates when a Phone Line Fail condition is detected. For
Steady or Pulse modes, the output remains activated until the condition
is cleared.
This output works independently of
Phone Line Fault
Response Options
(page 57).
0 13 Ack Received (any report) Output activates when the acknowledgement for any report is received.
For Steady or Pulse modes, [System Reset] resets. This output type is
event-driven. See Mode (Steady, Pulse, One Shot), Output ## on page 93
for more information.
0 14 AC Fail Output activates when a AC Fail condition is detected. For Steady or
Pulse modes, the output remains activated until the condition is cleared.
0 15 Low or Missing Battery Output activates when a control panel Low or Missing Battery condition
occurs. For Steady or Pulse modes, the output remains activated until
the condition is cleared.
1 0 PO 2 (on-board) Siren
Supervision Fail
Output activates when a Siren Supervision Fail condition is detected. For
Steady or Pulse modes, the output remains activated until the condition
is cleared and [System Reset] is pressed.
1 1 Sensor Trouble Monitor Output activates when a Sensor Trouble Monitor condition is detected in
conjunction with the selection made for the Sensor Monitor Time
setting. For Steady or Pulse modes, the output remains activated until
the Sensor Monitor Trouble condition is cleared.
1 2 Duress, [#][4][7] (reset)
resets
Output activates whenever a Duress PIN is entered. For Steady or Pulse
modes, the output remains activated until user presses [System Reset].
1 3 User Tamper, [#][4][7] (reset)
resets
Output activates on a User Tamper event. For Steady or Pulse modes,
the output remains activated until user presses [System Reset].
1 4 Arming Beeps (for
keyswitch/RF arming)
Disarm/All On/Perimeter Only/Partial On Beeps for keyswitch/RF arming.
1=Off, 2=All, 3=Perimeter Only. Mode and Time parameters do not apply.
This function works in conjunction with Address 1039 (See “Global
Output Options” in the
DS7200V2 Expert Programming Guide
(P/N:
4998153891)). Available for on-board outputs only.
1 5 Bell Time Starts on any
Alarm Event. PIN entry Stops.
Activates on Bell Test.
Output activates on any alarm event. Entering PIN terminates Bell Time.
For Steady and Pulse modes, the output remains activated for the
duration programmed in the Bell Time parameter.
1 6 Strobe Activates on Bell Time or output function as programmed. See “Strobe
Output Type Options” in the DS7200V2 Expert Programming Guide
(P/N: 4998153891). PIN entry resets the function.