Modular Fire Panel Installation | en 111
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
4.9.8 IOS0020A 20mA Communication Module
The 20mA communication module has an S1 interface, an RS232 interface (e.g. for
connecting a printer) and an S20 interface (20mA). The FAT2002 Fire Service Display Panel
or the THP2020A Thermal Printer is connected to the S20 interface. The Plena Voice Alarm
System can be connected via the RS232 interface.
Figure4.62: IOS0020A 20mA Communication Module
Labeling Connection
S1 IN | S1 OUT S1 interface
TX - | TX + | RX + | RX - S20 interface (20mA interface)
AUX - | AUX + Power supply +24VDC/max. 1.3A
RXD | TXD | GND RS232 interface
Assignment of DSUB9 Plug