Modular Fire Panel Installation | en 113
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
4.9.10 LSN0300A LSNimprovedModule 300mA
This module enables an LSN loop with up to 254 LSN improved elements or 127 classic LSN
elements to be connected, with a maximum line current of 300mA and a cable length of up to
1600m (depending on configuration and cable type).
Notice!
To ensure that the fire detection system is operated in compliance with EN 54‑13, each LSN
stub and T-tap must be terminated with EOL modules.
Figure4.66: LSN0300A LSNimprovedModule 300mA
Labeling Connection
LSN loop LSN stub
AUX1 + | AUX1 - Auxiliary power supply Auxiliary power supply for stub 1
LSN a1- | LSN b1+ LSN a1- / LSN b1+ outgoing Stub 1 LSN a1- / Stub 1 LSN b1+
AUX2 + | AUX2 - Auxiliary power supply* Auxiliary power supply for stub 2
LSN a2- | LSN b2+ LSN a2- / LSN b2+ incoming Stub 2 LSN a2- / Stub 2 LSN b2+
* The auxiliary voltage may only be fed back to AUX2 when isolators (ERT technology) are
used in the loop (suitable components include YBO-R/SCI isolators).
The technical data can be found in LSN0300A LSNimprovedModule 300mA, page 153.