12 en | Product Description Modular Fire Panel
09.2017 | 11.3 | F.01U.028.089 System Information Bosch Sicherheitssysteme GmbH
Networking
Up to 32panel controllers, remote keypads and OPC servers can be combined to form a
network.
Alarm Indication
The display element is an LCD touch screen with automatically activated backlighting. 12LEDs
provide continuous information about the operating status of the panel or system. Additional
LED indicator modules each with 16detection points can be used to provide visual indication
of alarms or faults.
Operation and Processing of Messages
The panel is operated and all messages are processed on the functionally designed operating
panel with the integrated LCD touch screen. There are permanent keys on the right, at the
bottom, and along the top of the display as well as variable virtual keys located in the touch
screen area.
The language for the menu navigation can be selected as required.
Below the status LEDs is a key switch with two programmable positions, e.g.:
for switching between day/night mode, or
for switching local alarm on/off (internal/external alarm)
Interfaces
A USB interface is provided to quickly transfer the required configuration to the panel
controller. There is also an Ethernet interface for adding the BIS software to the local network,
for example.
Saving and Printing Messages
All incoming messages and events are saved internally and can be viewed on the display at any
time. A log printer for printing incoming messages can be connected.
Installation
Information on installing the panel controller can be found in MPCPanel Controller, page 84.
The technical data can be found in MPC, page 148.
2.3 Remote Keypad
The FMR-5000-C Remote Keypad can be used to perform the same operating procedures as
the panel itself, enabling a networked system to be operated decentrally.
Power can be supplied by the panel or an external power supply unit such as the FPP-5000.
The easy-to-install housing was designed for tilted installation and for surface or flush wall
mounting.

Table of Contents

Other manuals for Bosch FPA-5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch FPA-5000 and is the answer not in the manual?

Bosch FPA-5000 Specifications

General IconGeneral
Max Number of Detectors per Loop254
DisplayLCD
Network CapabilityYes
Power Supply24 V DC
Operating Temperature-5°C to +50°C
Communication PortsEthernet
Humidity Range95% non-condensing