5 Commissioning
5.1 Notes
– Commissioning and the function test may only be carried out by authorized specialist
personnel.
– Observe all country-specific testing and acceptance regulations.
– A function test must be carried out before commissioning (see Functional Test, page 141).
Bosch Security Systems recommends at least one function test and one visual inspection
per year.
5.2 Documentation
The panel controller is supplied with a CD on which you will find the product documentation
(installation instructions, system description).
The current and full product documentation can also be found on the Internet at
www.boschsecurity.com.
The fire panel is configured on a PC using the FSP-5000-RPS programming software. The
programming software and the associated documentation can also be found on the CD
supplied with the FPA-5000. More recent versions of the software are available on the Internet
for those with access rights.
Information about the programming software is also included in the online help.
5.3 Quick Guide for Commissioning
1. Connect the panel to the power supply.
2. Connect the MPC Panel Controller to the PC (via USB). Make sure that the current
version of the FSP-5000-RPS programming software is installed on your PC.
3. Start the auto-configuration. Edit the configuration according to the requirements of the
fire detection system.
4. Load the configuration to the MPC Panel Controller.
5. Start the walktest.
6. Test the power supply (see Testing the Power Supply, page 142)
7. Check the conventional and LSN functions (see Testing the Conventional and LSN
Functions, page 142).
8. Test all detection points and activations as programmed (see Testing the Addressing/
Activation, page 142).
9. Read out the diagnosis file and save the file as a test log.
5.4 Functional Test
5.4.1 Preparation
Once all components of the fire detection system are installed and wired:
1. Turn on the fire detection system.