42 en | Installation Modular Fire Panel
09.2017 | 11.3 | F.01U.028.089 System Information Bosch Sicherheitssysteme GmbH
For installation reasons, only 42modules can be programmed when configuring a redundant
panel. Without redundancy, 46modules per panel are possible if one housing is set up with
the panel controller and 10modules and three housings each with 12modules.
Notice!
In line with EN54-2, a redundant panel controller must be used if there are more than 512
detectors connected.
4 Installation
4.1 General Information
Danger!
Some devices contain live components.
Touching live components entails a risk of death or serious injury.
Disconnect the power supply before all installation work.
!
Warning!
Electrostatic discharge.
The standard precautions for CMOS technology must be taken when handling PC boards.
The fire panel may only be installed and commissioned by trained specialist personnel.
Only use installation materials recommended by BOSCH Security Systems. Otherwise,
interference resistance cannot be guaranteed.
Connection conditions set down by the regional authorities and institutions (police, fire
service) must be observed.
Environmental Conditions
Fire panels can only be installed in dry, clean interior rooms.
The following environmental conditions must be noted:
Permissible ambient temperature: - 5°C to + 50°C
Permissible relative humidity: max. 95%, non-condensing
To ensure optimum battery service life, the panel should only be operated at sites with
normal room temperatures.
Do not operate devices showing condensation.
Positioning
Operating and display elements should be positioned at eye level.
The distance between the upper edge of the housing and the center of the panel
controller display is around 11cm. For example, if the eye level required is 164cm, the
housing upper edge installation dimension is 175cm.
For frame installation housings, a clearance of at least 230mm is required to the right of
the last housing to swivel out the installed housing (e.g. for connection, maintenance or
service).
Sufficient space should be left below and next to the panel for any possible extensions,
e.g. for an additional power supply or an extension housing.
The installation dimensions can be found in Installation Dimensions for Wall Mounting
Housing, page 47 to Installation Kits for 48cm (19”) Racks, page 59.