EasyManua.ls Logo

Bosch FPA-5000 - RMH 0002 a Relay Module for Mains Voltage

Bosch FPA-5000
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modular Fire Panel Installation | en 117
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
4.9.13 RMH 0002 A Relay Module for Mains Voltage
Danger!
The device contains live components.
Touching live components entails a risk of death or serious injury.
Disconnect the power supply before all installation work.
The module has two changeover contact relays (typeC) for monitored connection of external
elements with feedback, e.g.
Electromagnetic door holders
Fans
Smoke dampers
Each relay has one NO (normally open) and one NC (normally closed) contact and is protected
by a 6.3A fuse.
The outputs are not monitored.
The maximum permissible contact load is 5A at 120V/230VAC and 5A at 30VDC.
The relay module can also be used as an extinguishing system interface in accordance with
VdS2496.
Figure4.70: RMH 0002 A Relay Module for mains voltage
Labeling Connection
NC1 | C1 | NO1 Relay 1
NC2 | C2 | NO2 Relay 2
FB1 + | FB1 - Feedback relay 1
FB2 + | FB2 + Feedback relay 2
The technical data can be found in RMH 0002 A Relay Module for mains voltage, page 155.