Modular Fire Panel Installation | en 107
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
4.9.4 CZM0004A 4Zone Conventional Module
The CZM0004A Conventional Module enables particular existing conventional peripherals to
be connected. It provides connections for four monitored conventional lines.
Figure4.58: CZM0004A 4Zone Conventional Module
Labeling Connection
AUX1 + | AUX1 - 24VDC auxiliary power supply zone1
OUT1 - | OUT1 + Zone1 output low/zone1 output high
IN1 - | IN1 + Zone1 input low/zone1 input high
AUX2 + | AUX2 - 24VDC auxiliary power supply zone2
OUT2 - | OUT2 + Zone2 output low/zone2 output high
IN2 - | IN2 + ClassA zone2 input low/classA zone2 input high
AUX3 + | AUX3 - 24VDC auxiliary power supply zone3
OUT3 - | OUT3 + Zone3 output low/zone3 output high
IN3 - | IN3 + ClassA zone3 input low/classA zone3 input high
AUX4 + | AUX4 - 24VDC auxiliary power supply zone4
OUT4 - | OUT4 + Zone4 output low/zone4 output high
IN4 - | IN4 + ClassA zone4 input low/classA zone4 input high
Notes
– All additional voltage outputs (AUX1-AUX4) can be switched on and off simultaneously.
– Two and four-wire conventional components can be connected.
– Note the maximum line resistance:
– 25Ohm for conventional lines with FMC-300-RW or automatic fire detectors
– 12Ohm for conventional lines with FMC-120-DKM call points
Notice!
To ensure that operation of the fire detection system complies with EN 54-13, each
conventional line must be terminated with EOL modules.
The EOL modules can be used with CZM modules from software version 1.1.10 onwards.
The technical data can be found in CZM0004A 4Zone Conventional Module, page 151.
4.9.5 ENO0000B Fire Service Interface Module
The ENO 0000 B is used to connect fire service equipment: