Modular Fire Panel Planning | en 27
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
3.3 Detection Points
Each element or input that can trigger an alarm after programming requires its own detection
point. Detection points are enabled via address cards. One FPA‑5000 manages up to 4096
detection points.
All elements and inputs that do not use the Input type in the Message type setting are
regarded as detection points. Therefore, all elements and inputs for which one of the
following settings is programmed as the Message type are regarded as detection points:
– Fire
– Internal fire
– Building control
– Multi-criterion
– Smoke
– Fault
– Heat
– Water
Only some of these message types are available for selection depending on the element type.
The elements and inputs that can trigger an alarm include all manual and automatic detectors,
as well as the modules and interface modules listed below on the basis of the available inputs.
Modules Detection Points
CZM0004A Up to 4 (1 detection point per zone)
IOP0008A Up to 8 (1 detection point per monitored input)
ENO 0000 B requires 1 detection point only if a FSE release element is
connected and programmed using the FSP-5000-RPS
programming software
Interfaces Detection Points
FLM-420/4CON Up to 2
FLM-420-I8R1 Up to 8
FLM-420-I2 Up to 2
FLM-420-O8I2 Up to 2
FLM-420-O1I1 Up to 1
FLM-420-RLE-S Up to 2
3.4 Addressing
LSN elements are addressed via rotary switches (e.g. FAP420) or DIP switches (e.g. E/W
versions of the FLM-420).
For the detectors, there are three rotary switches on the underside, which can be used to
select automatic or manual addressing with or without automatic detection.
The following settings are possible:
Rotary switch setting Address Operating mode
0 0 0 Loop/stub in LSNimproved version mode with
automatic addressing (T-tapping not possible)=
factory default setting