26 en | Planning Modular Fire Panel
09.2017 | 11.3 | F.01U.028.089 System Information Bosch Sicherheitssysteme GmbH
The LSNimproved version allows T-taps on stubs or loops and any number of nodes, branches
per node and elements per branch as long as the maximum number of elements does not
exceed 254.
Connections can be positioned anywhere along the LSN line.
Notice!
Planning should take the anticipated total current and line resistance into account to ensure
each detector has an operating voltage of at least 15VDC.
As soon as an LSN classic device is in a loop or stub, only loop or stub structures can be
used. In this case, T-tapping is no longer possible.
4: 1 or 2 stubs and T-taps
mixed
5: Loop and stubs mixed with
T-taps
Table3.1: Possible structures in LSN
When configuring the detectors, it is essential to ensure that no mesh structures are created.
Mesh structures within a stub structure Mesh structures within a loop structure
Table3.2: Unusable network structures