Modular Fire Panel Technical Data | en 145
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
Number of functional modules Max. number
ANI 0016 A 32
BCM-0000-B 8
CZM 0004 A 32
ENO 0000 B 8
FPE-5000-UGM 4
IOP 0008 A 32
IOS 0020 A 4
IOS 0232 A 4
LSN 0300 A 32
LSN 1500 A 11
NZM 0002 A 8
RMH 0002 A 32
RML 0008 A 32
7.2 Power loss of FPA-5000 Components
Component Power loss
ANI 0016 A 0.62W (all LEDs lit)
BCM‑0000‑B – 0.96W (controller + green LED lit)
– 1.44W (per AUX with 1.06A load)
CZM 0004 A – 1.65W (for a line with 100mA load)
– 3.36W (for 4 lines with 100mA load each)
ENO 0000 B – 1.44W (1 relay activated)
– 7.80W (4 relays activated + key deposit heating
active)
FMR-5000-C 5.52 W
FPE-5000-UGM 0.17W
IOP 0008 A 0.24W
IOS 0020 A 0.36W
IOS 0232 A 0.36W
LSN 0300 A – 1.50W (AUX with 490mA load)
– 2.72W (LSN)
LSN 1500 A – 8.00W (AUX)
– 14.70W (LSN with 750mA load)
MPC-xxxx-C 5.40W
NZM 0002 A 0.96W
PRD 0004 A 0.07W