36 en | Planning Modular Fire Panel
09.2017 | 11.3 | F.01U.028.089 System Information Bosch Sicherheitssysteme GmbH
HCP0006A, Fully Configured Panel, with Installation Sequence
Figure3.6: Example of configuration with HCP0006A Modular Panel Housing for 6 Modules
3.8 Configuration of BCM Battery Controller Module
The panel can be powered by up to 8 BCM-0000-B Battery Controller Modules, each with its
own UPS2416A Universal Power Supply. Current consumption is equally distributed among
all battery controller modules.
Notes
– The 24V switch outputs may not be connected in parallel.
– The total current for all connected components including the battery charge current may
not exceed 6A.