Modular Fire Panel Installation | en 121
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
Type designation Connection of ... ... to Document number
CBB 0000 A 1) BCM Battery Controller
Module
Battery pair F.01U.003.099
CPA 0000 A MPC Panel Controller FMA-AT2000-IP/-ISDN/-GSM, ENO0000B F.01U.003.343
CPB 0000 A BCM Battery Controller
Module
UPS Universal Power Supply F.01U.003.098
CPR 0001 A MPC Panel Controller RLE 0000 A Junction Board F.01U.003.342
CRP 0000 A MPC Panel Controller MPC Panel Controller (Redundant) F.01U.003.097
1) Required for power supply in a separate power supply housing. Compared to the enclosed standard cable sets,
this cable set has a longer connecting cable to the battery.
Notice!
In the installation instructions for the CPA0000A Cable Set: Please refer to the programming
instructions for the FMA-AT2000‑IP/-ISDN/-GSM.
4.11 Monitoring auxiliary power according to EN54-13
Auxiliary power supplies to the following modules can be monitored for creeping short circuits
and creeping wire breaks: LSN 300, LSN 1500, and BCM-0000-B (when using FPP-5000-TI13).
A creeping short circuit is detected by these modules. An FPP-5000-TI13 forwards the faults
detected and reported by the BCM-000-B to the panel. Use additional 4-wire end of line
elements to monitor for creeping wire break.
Procedure:
1. Monitor with 4-wire end of line element:
– On stub cabling, terminate the exposed end of an AUX line with an FLM-420-EOL4W
– Insert an FLM-420-EOL4W as the last element of an LSN ring or of a stub
– Use an FLM-320-EOL4W for the conventional zone of a conventional zone module or
a FLM-420-CON/4
2. Activate EN 54-13 compliant operation.
Notice!
According to EN 54-13, no branch wiring (T-tapping) is permitted for auxiliary power supplies.
4.12 FPP‑5000 External Power Supply Unit Kit 24V/6A
The FPP-5000 External Power Supply Unit Kit is designed to provide a universal power supply,
and has space for two 12V/45Ah batteries.
Figure4.76: FPP‑5000 External Power Supply Unit Kit 24V/6A