122 en | Installation Modular Fire Panel
09.2017 | 11.3 | F.01U.028.089 System Information Bosch Sicherheitssysteme GmbH
Scope of Delivery
– PMF 0002 A Power Supply Housing Frame Installation medium
– FMH 0000 A Mounting Frame Medium
– Power supply bracket, installed
– UPS 2416 A Universal Power Supply
– PRS-0002-C Panel Rail Short
– BCM-0000-B Battery Controller Module
– Requisite cable sets
Can be Extended with:
– 2 x 12V/45Ah batteries
– FPP‑5000‑TI Trouble Interface or FPP-5000-TI13 LSN Communication Interface
– FPO‑5000‑EB Earth Bar
Notes
– You can find the installation instructions for the FPP-5000 kit at www.boschsecurity.com
by searching for the type designation (document number for installation instructions:
F.01U.005.065).
– The installation dimensions are the same as those for the PMF0004A (see ).
FPP‑5000‑TITrouble Interface
The FPP-5000-TImodule is used in the FPP-5000 External Power Supply Unit with the
BCM-0000-B to transmit faults to the fire panel via the Local Security Network (LSN).
Two independent signal inputs for "battery fault" and "mains current fault" allow a specified
fault indication on the fire panel.
The FPP-5000-TI is connected directly to the LSN bus line and supplied with power via the bus
line.
Figure4.77: FPP‑5000‑TITrouble Interface
Labeling Connection
AUX1 - | AUX1 + Auxiliary power supply, incoming
LSN1 a1 - | LSN1 b1 + LSN in
SHIELD Shield wire
AUX2 - | AUX2 + Auxiliary power supply, outgoing
(support points for looping through)
LSN1 a2 - | LSN1 b2 + LSN outgoing
AC FAULT - | + Input of mains fault
BATT FAULT - | + Input of battery fault