Modular Fire Panel Appendix | en 157
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
Installation of the power supply unit is described in RMH 0002 A Relay Module for Mains
Voltage, page 117.
7.6.2 FPP‑5000‑TITrouble Interface
Input voltage 15VDC to 30VDC
Maximum current consumption 1.15mA (at 24V), from LSN
Protection class (IEC60529) IP20
Addressing using eight DIP switches
Space required (H x W x D) approx. 127 x 96 x 60mm
The module is described in FPP‑5000 External Power Supply Unit Kit 24V/6A, page 121.
7.6.3 FPP‑5000‑TI13 Communication Interface
Input voltage 15VDC to 33VDC
Current consumption
– From panel rail at 24VDC
– From LSN
– 13.2mA
– 3.25mA
Protection class (IEC60529) IP20
Space required (H x W x D) approx. 127 x 96 x 60mm
The module is described in FPP‑5000 External Power Supply Unit Kit 24V/6A, page 121.
8 Appendix
8.1 Options with requirements under EN 54‑2:1997/A1:2006
The FPA-5000 provides the following options with requirements under EN 54‑2:1997/A1:2006:
– Output for activation of fire alarm devices
– Activation of fire alarm transmission equipment
– Output to fire alarm transmission equipment
– Alarm acknowledgement input from fire alarm transmission equipment
– Output for activation of fire protection equipment
– Output type A
– Output type B
– Output type C
– Fault monitoring of fire protection equipment
– Transmission delay
– Dependency of fire detection status on more than one alarm signal
– Type A dependency
– Type B dependency
– Alarm counter
– Fault signal status
– Fault signals from detection points
– Complete failure of power supply
– Output to fault signaling transmission equipment
– Disabled status
– Disabling of addressable points
– Test status