Modular Fire Panel Technical Data | en 155
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
Installation of the power supply unit is described in LSN1500A LSN improved Module
1500mA, page 114.
7.5.11 NZM0002A Notification Appliance Zone Module
Operating and display elements 4 LEDs (2xred, alarm/2xyellow, fault)
2 buttons (LED test)
Input voltage 20VDC to 30VDC/5VDC ± 5%
Maximum current consumption
Standby mode (both zones) 40mA
In case of alarms (both zones) 65mA + 500mA per notification appliance
Maximum output voltage 29.5VDC
Maximum output current
For supply via panel rail 500mA per notification appliance (in case of
alarm)
For external power supply 3A per notification appliance (in case of
alarm)
Space required (H x W x D) approx. 127 x 96 x 60mm
Weight Approx. 135g
Installation of the power supply unit is described in NZM0002A Notification Appliance Zone
Module, page 116.
7.5.12 RMH 0002 A Relay Module for mains voltage
Operating and display elements 4 LEDs (2xred, alarm/2xyellow, fault)
2buttons (each on/off)
Fuses F1 = T6.3A, F2 = T6.3A
Input voltage 20VDC to 30VDC/5VDC ± 5%
Feedback current max. 8.5mA per feedback output
Feedback voltage max. 30VDC
Maximum current consumption
Standby operation 10mA
Both relays tripped 50mA
Maximum contact load 5A at 120V/230VAC or 5A at 30VDC
(resistive)
Maximum line resistance of feedback lines 2x25Ω
Space required (H x W x D) approx. 127 x 96 x 60mm
Weight Approx. 135g
Installation of the power supply unit is described in RMH 0002 A Relay Module for Mains
Voltage, page 117.