Modular Fire Panel Planning | en 37
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
– The batteries connected to the BCM must all be of the same type and have identical
electrical properties.
– The cable length at the switch outputs for faults may not exceed 3meters.
– The cables for the switch outputs for faults may only be routed inside the housing.
Information on installation of the BCM module can be found in BCM‑0000‑B Battery Controller
Module, page 101.
Configuration with One to Four BCM Modules in Wall Mounting Housings
– Up to 2 BCM-0000-B modules on short panel rail
– Maximum 2 BCM-0000-B modules at the end of the long panel rail
– Each BCM-0000-B module requires one UPS 2416 A Universal Power Supply.
Figure3.7: Configuration of 1 to 4 BCM modules (wall mounting)
Configuration with One to Four BCM Modules in Frame Installation Housings
– Up to 2 BCM-0000-B modules on short panel rail
– Maximum 2 BCM-0000-B modules at the end of the last long panel rail