Modular Fire Panel Product Description | en 17
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
The HCP0006A and HBC0010A basic housings can be extended to meet individual
requirements using:
HBE0012A Modular Extension Housing for an additional 12modules, and 2 x 12V/28Ah
batteries
PSS0002A or PSB0004A Power Supply housings for additional power supply units and
12V/28Ah batteries
DIB0000A Distribution Box
The DIB 0000 A Distribution Box is equipped with a distributor rail and is used to install
terminal strips.
Equipment Limits
The table below shows the maximum number of:
Modules
Panel rails (short PRS-0002-C, long PRD 0004 A)
Housing type Modules Short rail Long rail
HCP 0006 A 6 1 1
HBC 0010 A 10 1 2
HBE 0012 A 12 - 3
PSS 0002 A - - -
PSB 0004 A - - -
DIB 0000 A - - -
The table below shows the maximum number of:
Panel controllers
UPS power supply units
Batteries
Housing type MPC UPS power supply
units
Batteries
HCP 0006 A 1 1 2x28Ah
HBC 0010 A 1 1 2x28Ah
HBE 0012 A - 1 2x28Ah
PSS 0002 A - 1 2x28Ah
PSB 0004 A - 1 4x28Ah
DIB 0000 A - - -
Installation Types
Various types of installation are possible:
Surface mounted
Installation in 482.6mm (19") racks
For surface mounting, the housing is mounted directly on the wall. For installation in
482.6mm (19") racks, the FRK0019A installation kit is used.
The housings have pre-formed cable bushings.
Front Doors
The housings can also be equipped with transparent front doors. The doors are made of
impact-resistant plastic and are available in two sizes (each with a lock on the left or right).