Modular Fire Panel Planning | en 29
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
n
E
= number of elements
ρ = specific resistance of copper = 0.0178Ωmm
2
/m)
R
FET
= FET resistance = 0.7Ω (LSN classic) or 0.35Ω (LSN improved),
I
NE
= average current consumption of elements in[A]
I
trans
= transmission current = 0.012A
I
flash
= flash current = 0.018A
Note that the sum of non-isolated cables must not exceed the limit of 500m. The limit of
500m applies to:
– The lines on the inputs of the following modules: FLM-420-RHV, FLM-420-I2 , FLM-420-
I8R1-S, FLM-420-O8I2-S, FLM-420-O1I1, FLM-420-RLE-S
– The NAC line of the FLM-420-NAC module
– The lines to remote indicators: FAA-420-RI-DIN, FAA-420-RI-ROW
The limit of 500m non-isolated cables doesn't count for the conventional lines of the
FLM-420/4‑CON and the lines connected to the relay contacts and open collector outputs.
Note that the maximum cable length must not exceed 1600m.
Using the Diagram for LSN classic
FET resistance = 0.7Ω, fire alarm cable with Ø0.8mm
Example 1:
You want to know the maximum cable length for a given number of network elements and a
given current consumption (n
E
=50, I
NE
=3 mA). On the X axis, go vertically up at 50 until you
reach the 3mA curve. Then, from the point of intersection go horizontally to the left to the Y
axis and read off the maximum achievable cable length. In this example it is 840m.
Example 2:
You want to know the maximum number of network elements for a given cable length and an
average current consumption of the network elements (L=1000m, I
NE
=20mA). Starting from
the Y axis at 1000, go horizontally across to the right as far as the 20mA curve and then from
the point of intersection vertically down to the X axis. Read off the maximum number of
network elements, in this example it is 8.
Notice!
Remote indicators activated by the detector C point:
A maximum additional cable length of 500m is allowed when using remote indicators (e.g.
FAA-420-RI-DIN/FAA-420-RI-ROW). The total length of installed cable must not exceed the
limit of 1600m.