Modular Fire Panel Installation | en 73
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
The temperature-dependent output voltage is monitored and regulated by the BCMBattery
Controller Module.
The output voltage is monitored and regulated by a temperature sensor. If there is a fault, the
FAULT output drops to 0V.
!
Warning!
The power supply unit may only be used in the specially designed brackets and in a fireproof
cover (such as a panel housing).
!
Warning!
There is a risk of injury if the temperature sensor is not positioned between the batteries.
The temperature sensor is supplied with the power supply bracket and protects the batteries
against overheating. If the sensor is not positioned correctly, the batteries can overheat and
explode.
Position the temperature sensor between the batteries.
1234 5678
LED
1 8
Figure4.28: UPS2416A Universal Power Supply 24V/6A
Pos. Labeling Connection
1 - 2 ACL | ACN Mains supply
3 Protective ground
4 - 5 DC+ | DC- 26.76VDC output plus/0VDC output minus
6 FAULT Mains fault output

Table of Contents