24-Hour Trouble: If faulted, a trouble condition always occurs. To restore a 24-hour
trouble point, turn they system off if it is on, or acknowledge the alarm if the system is
off.
User Emergency, 24-hour supervisory point type:
If the point's circuit style = 0, an open or shorted circuit creates a tamper condition.
An off-normal circuit creates an alarm condition.
If the point's circuit style = 1, an open or shorted circuit creates an alarm condition.
Refer to Circuit Style on page 68 for more information.
If User Emergency is assigned to a wireless detector, any off-normal alarm condition
creates an alarm condition.
To restore a user emergency point, turn the system off if it is on, or acknowledge the
alarm if the system is off.
9xx6. Alarm Verification
Select whether or not the central station can verify the alarm when it receives an alarm report
from the point and the report is acknowledged.
Country Codes
The country code sets the control panel to the appropriate country-specific defaults for your
installation.
Country Code Country Code
Argentina 01 Israel 63
Australia 02 Italy 25
Austria 03 Japan 26
Belarus 62 Lithuania 29
Belgium 04 Luxembourg 20
Bosnia 65 Malaysia 32
Brazil 05 Mexico 34
Bulgaria 06 Netherlands 35
Canada 07 New Zealand 36
China 08 Norway 38
Croatia 10 Poland 41
Czech Republic 12 Portugal 42
Denmark 13 Romania 43
Egypt 14 Russian Federation 44
Finland 16 Spain 51
France 17 Sweden 52
Germany 18 Taiwan 54
Greece 19 Thailand 55
Hong Kong 20 Turkey 56
Hungary 21 Ukraine 62
9.2
Easy Series Control Panel Programming Details and Defaults | en 111
Bosch Security Systems, Inc. System Reference Guide 2014.09 | 01 | F.01U.306.221