Paragraph
Number in
ANSI/SIA CP-01
Feature Requirement Range Shipping
Default
Recommended
Programming
1
4.2.6.1 and 4.2.6.2 Duress Feature Allowed Option No 1+ derivative of
another user code;
no duplicates of
other user codes
Disabled Disabled
4.3.1 Cross Zoning Required Option Programming
needed
Disabled Enabled and two
or more zones
programmed
4.3.1 Programmable
Cross Zoning Time
Allowed Can program Per
manufacturer
Per walk path in
protected
premises
4.3.2 Swinger
Shutdown
Required
(programmable)
For all non-fire
zones, shut down
at one or two
faults
One fault One fault
4.3.2 Swinger
Shutdown Disable
Allowed For non-police
response zones
Enabled Enabled (all
zones)
4.3.3 Fire Alarm
Verification
Required option Depends on
control panel and
sensors
Disabled Enabled unless
sensors can self-
verify
4.5 Call Waiting
Cancel
Required option Depends on user
phone line
Disabled Enabled if user
has call waiting
1
Programming at installation site might be subordinate to other UL requirements for the intended application.
2
Combined Entry Delay and Abort Window should not exceed 1 minute.
3
If the cross zone timer ends and a second cross zone point is not faulted, the system sends an intrusion alarm
unverified report.
Underwriters Laboratories (UL)
Household Fire Warning System
Install at least one UL Listed four-wire latching type smoke detector rated to operate over
the voltage range of 11.2 VDC to 12.3 VDC. The maximum smoke detector load is 50 mA.
Install one UL Listed 85 dB audible device rated to operate over the range of 11.2 VDC to
12.3 VDC as required for this application. Program the bell cut-off time for at least four
minutes. Refer to Programming Item 107 in System Programming Items, page 48.
Install end-of-line resistor P/N: 47819 after last smoke detector.
Do not use a printer interface module.
Where two-wire addressable devices are used, do not place fire and intrusion devices on
the same zone.
The system must be able to operate for at least 24 hr, and generate a full alarm output for
at least 4 min without AC power.
Household Burglar Alarm Unit
Install at least one UL Listed 85 dB audible device rated to operate over the voltage range
of 11.2 VDC to 12.3 VDC.
1.5
Easy Series Control Panel Agency Approvals and Requirements | en 9
Bosch Security Systems, Inc. System Reference Guide 2014.09 | 01 | F.01U.306.221