Route Power-limited Wiring
All wiring except primary AC power and standby battery is power-limited. Separate primary AC
power and standby battery wires from other wires by at least 6.4 mm (¼ in), and secure to
enclosure to prevent movement. Primary AC power and standby battery wiring cannot share
the same conduit, conduit fittings, or conduit knockouts with any other wiring. Refer to the
figure below.
Figure 3.2: Power-limited Wire Routing
Install the B450 with a compatible B44x
The control panel supports one B450 Conettix Plug-in Communicator Interface for cellular
connectivity.
Setting the bus address
The B450 Conettix Plug-in Communicator Interface address switch provides the value for the
module's address. Set the address to 6.
Insert the communication module
Insert the B44x into the B450 according to the B450 Conettix Plug-in Communicator Interface
(B450) Installation and Operation Guide (P/N: F01U300740).
Notice!
It is recommended to wire the B450 module to the control panel via the terminal strip prior to
mounting the B450 into the enclosure. Failure to do so will complicate the mounting
procedure.
All communicators shall be housed in tampered enclosures. If the unit is used in a commercial
burglar environment, and is enclosed in a commercial enclosure, that enclosure must be
tampered.
If the installation is a local or police station connection, then the B450 must be mounted
inside an attack resistant enclosure.