Temperature (operating) Functional range: -10゚C to +49゚(+14゚F to +120゚F)
EN 50130-5 Class II only: -10゚C to 40゚C (+14゚F to +104゚
F)
Relative humidity 0% to 93% (non-condensing)
Cover and wall tamper switch Transmits a tamper switch signal when the detector is
removed from its base, or the unit is pulled away from
the wall.
Drift compensation adjustment -1.64%/m (0.5%/ft) maximum
Sounder 85 dBA at 3 m
Self-diagnostics feature Monitors detector sensitivity and operational status.
Frequency 433.42 MHz
Table 8.9: Specifications
Figure 8.5: Smoke detector
1 ᅳ High intensity LED
2 ᅳ Test/Silence button
Battery replacement
Under normal conditions, the LED normally flashes every 8 sec to indicate normal operating
conditions. Replace the battery when the LED stops flashing, and the sensor chirps every 45
sec.
Silence the low battery trouble chirps for 24 hr by pushing the Test/Silence button. Refer to
the Smoke detector illustration for locating the Test/Silence button.
Smoke test
Test smoke detectors annually by using a listed aerosol smoke tester to simulate an alarm.
Follow the instructions on the can.
The LED should remain ON while the detector provides a continuous tone. The detector
automatically resets when smoke is no longer present. A detector that fails to activate with
the smoke test might require cleaning or replacement.
Notice!
To avoid a fire department dispatch, contact central monitoring station, or put the system
into Test mode before activating the detector using this method.
8.11.1
8.11.2
88 en | Device Specifications and Overview Easy Series Control Panel