– Sends a Recent Closing report for any alarm that occurs within two minutes of the end of
Exit Delay
– Includes a Fire Verified point type option that is disabled by default
Quick Reference
Refer to the following table for programmable features, shipping defaults, and recommended
programming that comply with the ANSI/SIA CP-01 False Alarm Reduction standard.
The system test button tests all points, all outputs, the control panel, and the communicator.
Refer to Test the System, page 66 for more information.
Paragraph
Number in
ANSI/SIA CP-01
Feature Requirement Range Shipping
Default
Recommended
Programming
1
4.2.2.1 Exit Time Required
(programmable)
For full or auto
arming: 45 sec to2
min (255 sec max)
60 sec 60 sec
4.2.2.2 Progress
Annunciation/
Disable for Silent
Exit
Allowed Individual control
centers can be
disabled.
All control
centers
enabled.
All control
centers enabled.
4.2.2.3 Exit Time Restart Required Option For re-entry during
Exit Time
Enabled Enabled
4.2.2.5 Auto Stay Arm on
Unvacated
Premises
Required
option(except for
remote arm)
If no exit after full
arm
Enabled Enabled
4.2.4.4 Exit Time and
Progress
Annunciation/
Disable for
Remote Arm
Allowed option
(for remote arm)
Can be disabled
for remote arm
Enabled Enabled
4.2.3.1 Entry Delay(s) Required
(programmable)
30 sec to 4 min
2
30 sec At least 30 sec
2
4.2.5.1 Abort Window for
Non-fire Zones
Required option Can be disabled
by zone or zone
type
Enabled Enabled (all
zones)
4.2.5.1 Abort Window
Time for Non-fire
Zones
Required
(programmable)
15 sec to 45 sec
2
30 sec At least 15 sec
2
4.2.5.1.2 Abort
Annunciation
Required option Annunciate that no
alarm was
transmitted
Enabled Enabled
4.2.5.4.1 Cancel
Annunciation
Required option Annunciate that a
Cancel was
transmitted
Enabled Enabled
8 en | Agency Approvals and Requirements Easy Series Control Panel
2014.09 | 01 | F.01U.306.221 System Reference Guide Bosch Security Systems, Inc.