Loading...
9-22
Bosch Security Systems 09/11 BLCC500I
Solution 16i
Installation Manual Comms Programming
Comms > Comms Test > L593
Test Report Options
MENU 5-9-3
1 Send Test Reports Only If No Other Report N
2 Send Test Reports On Audible Time Out Y
3 Reserved N
4 Reserved N
5 Reserved N
6 Reserved N
7 Reserved N
8 Reserved N
1) Enter your Installer PIN + [MENU].
2) Enter [5] + [9] + [3] + [OK].
The keypad will display the current options which are
selected or enabled.
-bit-
2
3) Use the numeric keys [1] to [8] to turn on and o
the features as required. When the corresponding
number on the keypad is on then the option is
selected.
4) When all email options are programmed, press [OK]
to save and exit, or press [MENU] to exit without
saving.
Send Test Reports Only If No Other Report
Setting this option will cause the system to only send its
automatic Test report if no other area report has been
sent within the test report time period as programmed in
MENU 5-9-2.
Send Test Reports On Audible Time Out
Setting this option will delay the Automatic Test Report if
the sirens are running when the test report time expires.
This eectively keeps the telco line free to make any
further alarm reports which may be triggered while the
sirens are running. The panel will send the cued Test
Report as soon as the siren run-time has expired.
Comms > Comms Test > L594
Test Route
MENU 5-9-4
(*** System Wide Parameter ***)
0 1
00 = Report Events To Log Only
01 = Report Events To Destination 1 + Log
02 = Report Events To Destination 2 + Log
03 = Report Events To Destination 1 & Destination 2 + Log
04 = Report Events To Dest 2 If Dest 1 Fails + Log
This menu programs which destination will be used to
send both manual and automatic test reports.
1) Enter your Installer PIN + [MENU].
2) Enter [5] + [9] + [4] + [OK]. The keypad will display
the current Test Route.
d= 01
3) Use the numeric keys to enter the Test Route
required, then press [OK] to save and exit or press
[MENU] to exit without saving.
Comms > Comms Test > L595
Dial Number Test
MENU 5-9-5
This option provides a quick and easy way for the Installer
to test the communication path for the panel while they
are onsite without the need to trigger test reports and then
verify them with the base station. Once the telco wiring
has been completed, enter your mobile phone or another
test number into this location and press [OK]. The panel
will then seize the phone line and dial the programmed
number.
1) Enter your Installer PIN + [MENU].
2) Enter [5] + [9] + [5] + [OK]. The keypad will prompt
you to enter a telephone number.
_
3) Using the numeric keys [0] to [9], enter all the digits
of the telephone number. For special characters
including, pause, * or #, use the up and down
arrow keys.
4) Press [OK] to commence the dialler number test.
i
Note
The panel will make only one attempt to call this
number per activation. To perform multiple tests
repeat the sequence. There is no need to answer the
test call.