Error Code Display Symbol Error Description Corrective Action
22 Er 22
Timing error: check-sum
error received during
multi-chip
communication
procedure
1. Correct the multi-chip
communication software
to meet the protocol
requirement.
2. Return to factory for
repair.
23 Er 23
Timing error: wrong
function code received
during multi-chip
communication
procedure
1. Correct the multi-chip
communication software
to meet the protocol
requirement.
2.Return to factory for
Repair.
26 AtEr
Fail to perform
auto-tuning function
1.The PID values
obtained after auto-
tuning procedure are out
of range.Retry auto-
tuning.
2.Don't change set point
value during auto-tuning
procedure.
3 .Don’t change Event
input state during auto-
tuning procedure.
4.Use manual tuning
instead of auto-tuning.
27 CAER
Incorrect calibration
procedure or tolerance
of analog component too
big to meet specified
accuracy
1.Pay more attention to
the calibration
procedures.
2.Return to factory for
repair.

Table of Contents

Other manuals for Brainchild PR Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Brainchild PR Series and is the answer not in the manual?

Brainchild PR Series Specifications

General IconGeneral
BrandBrainchild
ModelPR Series
CategoryControl Unit
LanguageEnglish