Basic Control SiEN18-622
98 Function
Heating Operation
TcS = TcS initial value + KTc2
KTc2 : Correction value by ΔD signal in heating.
Δ D control
Keep the current KTc2
KTc2 = KTc2 + 0.5 KTc2 = KTc2 - 0.5
(Q0397)
KTc2 = 0
(without correction)
Not during compressor frequency PI
control
During compressor frequency PI
control (KTc2 = 0)
Down control by Δ D signal
continues 120 sec.
Up control by Δ D signal
continues 120 sec.