EasyManua.ls Logo

Daikin Super Multi Plus E-Series - Sky Air Indoor Unit Error Codes and LED Indication; Skyair Indoor Unit Error Codes and LED Indication

Daikin Super Multi Plus E-Series
456 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiEN18-622 Service Check Function
Troubleshooting 315
2.5 Sky Air Indoor Unit Error Codes and LED Indication
Symbols 5 : Blinks 4 : On 3 : Off — : No connection with troubleshooting
: High probability of malfunction
{ : Possibility of malfunction
: Low probability of malfunction
— : No possibility of malfunction (do not replace)
System
Indoor Unit
Remote
Control
Display
Location of Malfunction Contents of Malfunction
Details of
Malfunction
(Reference
Page)
Other
than PC
Board
PC Board
Outdoor
Unit
Indoor
Unit
Remote
Control
U5 {{Transmission error (between
indoor and remote control)
347
U8 {{Transmission error between
“main” remote control and
“sub” remote control
348
UA { Excessive indoor units
connected to this system.
349
Indoor
Unit
LED
Display
(H1P)
Remote
Control
Display
Location of Malfunction Contents of Malfunction
Details of
Malfunction
(Reference
Page)
Other
than PC
Board
PC Board
Outdoor
Unit
Indoor
Unit
Remote
Control
5
————Normal to outdoor unit
5
A1 ——{ Failure of indoor unit PC
board (For self-diagnosis by
LED, refer to p.304.)
333
4
3
5
A3 Malfunction of drain water
level system
334
5
AF Float switch operation
during compressor stop
336
5
A6
(FHQ only)
Indoor unit fan motor
overload / overcurrent / lock
337, 338
5
A7 Swing flap motor
Malfunction / Lock
340
5
AJ { Failure of capacity setting 342
5
C4 Malfunction of heat
exchanger temperature
sensor system (R2T)
343
5
C5 Malfunction of heat
exchanger temperature
sensor system (R3T)
344
5
C9 Malfunction of suction air
temperature sensor system
345
5
CJ —— Malfunction of remote
control air temperature
sensor system
346

Table of Contents