Troubleshooting for SkyAir Indoor Unit SiEN18-622
340 Troubleshooting
5.6 Swing Flap Motor Malfunction / Lock
Remote Control
Display
A7
Applicable
Models
FHQ
Method of
Malfunction
Detection
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Decision
Conditions
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
motor is energized for a specified amount of time (about 30 seconds).
Supposed
Causes
Failure of motor
Failure of microswitch
Failure of connector connection
Failure of indoor unit PCB