EasyManua.ls Logo

Daikin Super Multi Plus E-Series - Low Pressure Protection Control

Daikin Super Multi Plus E-Series
456 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Protection Control SiEN18-622
108 Function
4.2 Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
[In cooling operation]
[In heating operation]
Pe<0.25MPa
36Hz Unload
Pe>0.39MPa
Pe<0.07MPa
Low pressure not limited
Low pressure
standby
Pe<0.15MPa Pe>0.30MPa
Hot gas SVP = OFF
Hot gas SVP = ON
Pe: LP pressure sensor detection
value
Low pressure
limited
When occurring 3 times within 30 min., the
malfunction code "E4" is output.
&
• Ts-Teg<8deg
• Pe>0.06MPa
• Pe>0.09MPa
or
After 10 sec.Pe<0.17MPa
Pe<0.17MPa
Pe>0.20MPa
Pe< 0.07MPa
Current step limited
After 15 sec.
Low pressure not limited
Low pressure limited
INV upper limit frequency :
1-step up from current
compressor frequency
Pe: LP pressure sensor detection
value
INV upper limit frequency :
3-step down from current
compressor frequency
When occurring 3 times within 30 min.,
the malfunction code "E4" is output.
Pe<0.12MPa Pe>0.17MPa
Hot gas SVP = OFF
Hot gas SVP = ON
Low pressure
standby

Table of Contents

Related product manuals