EasyManua.ls Logo

Daikin Super Multi Plus E-Series - Malfunction of Transmission between Central Remote Control and Indoor Unit

Daikin Super Multi Plus E-Series
456 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting for Outdoor Unit SiEN18-622
400 Troubleshooting
7.35 Malfunction of Transmission between Central Remote
Control and Indoor Unit
Remote Control
Display
UE
Applicable
Models
AII indoor unit models
Centralized controller
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized remote control is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control and indoor
unit
Connector for setting master controller is disconnected.
Failure of PCB for centralized remote control
Defect of indoor unit PCB

Table of Contents

Related product manuals